====== Data Center ====== The Next Generation Data Center, delivered at the end of November 2017 and operational in December 2017.\\ Urbanized with 65 48U and 33 InRow racks, it hosts:\\ - 15 racks for the administrative IT department\\ - eight-rack research lab computer labs\\ - Grid 5000 servers, four racks\\ - CBP's eight-rack servers\\ - HPC servers (high-density up to 21kW per rack) of the PSMN 30 racks\\ in five specific cubes individually monitored.\\ The room area is about 200 m² and the IT power is scalable from 650 kW to 850 kW. The total electrical power available is that of a 20,000-volt cell.\\ Three inverters (all secured by batteries) deliver a power of 750 KW:\\ * A 400 watt inverter with a six-minute run time at full load for the HPC.\\ * A 200-kW inverter with a 30-minute run time at full load for the DSI.\\ * One 150kW UPS with 20 minutes of full load time for storage and labs.\\ Finally, there is still a reserve of more than 200 KW not corrugated, not secured by battery.